Images are for illustrative purposes only. Actual product may vary.
450-AKXB 1100W -48V DC Hot-Plug PSU, Non-Redundant (1+0), 60mm Form Factor
Dell 450-AKXB is a single 1100 W hot-plug power supply in Dell's 60 mm form factor that runs on -48 to -60 V DC input. Not for AC power.
Also known as · Dell 1100W -48V DC PSU · Dell 1100W LVDC power supply · Dell 1100W DC 60mm PSU
1-YR ZAYNTEK WARRANTY
Overview
The Dell 450-AKXB is a hot-plug server power supply rated at 1100 W that takes low-voltage DC input (-48 V to -60 V DC) rather than mains AC. It is meant for facilities that distribute -48 V DC power, such as telecom central offices, carrier colocation, and edge sites.
This SKU ships one PSU in a non-redundant (1+0) configuration. For redundant (1+1) operation, a second matching DC unit is installed in the server's other PSU bay. The module uses Dell's compact 60 mm PSU form factor.
Important: the unit works only on a DC supply. It cannot be connected to a 100–240 V AC circuit, and it should not be mixed with AC power supplies in the same server. Size the power budget for the full server configuration before deployment.
Specifications
Power Supply
| Dell part number | 450-AKXB |
|---|---|
| Rated output | 1100 W |
| Input type | DC only (-48 V DC); will not operate on AC power |
| Input voltage range | -48 V to -60 V DC (low-voltage DC) |
| Configuration | Single PSU, non-redundant (1+0) |
| Hot-plug | Yes |
| Form factor | 60 mm hot-plug PSU |
| Maximum heat dissipation | 4,265 BTU/hr |
| Rated input current | 27 A |
| Efficiency (10% / 20% / 50% / 100% load) | 85% / 90% / 92% / 90% |
| Efficiency class | None listed (Dell gives no 80 PLUS class for the DC unit) |
Related part numbers
| Related service part (DPN) | WPJC6 (1100 W -48 to -60 V DC, 60 mm) |
|---|
| Category | UPS & Power |
|---|---|
| Warranty | 1-year ZaynTek |
§ 04Questions
Can the Dell 450-AKXB run on standard AC power?
No. It is a DC-input supply designed for -48 V to -60 V DC power distribution. Connecting it to a 100–240 V AC circuit is not supported.
What does 'Non Redundant (1+0)' mean for this PSU?
The SKU supplies one power supply. A server running on it has no PSU redundancy. For 1+1 redundancy, a second matching 1100 W DC unit goes in the second PSU bay.
What input voltage range does the 1100 W DC PSU accept?
It accepts -48 V to -60 V DC input.
Can I mix this DC supply with an AC power supply in one server?
No. Both installed power supplies should be the same type and wattage, so do not pair a DC unit with an AC unit.
How much heat does the 1100 W -48 V DC PSU produce?
It is rated at up to 4,265 BTU/hr of heat dissipation, with a 27 A input current.